Compact Operating Instructions – DOP11C
27
4
Connecting the operator panel
Installation
Pin assignment for DOP11C:
Cable specification Use a 2 x 2-core twisted and shielded copper cable (data transmission cable with
braided copper shield). The cable must meet the following specifications:
Core cross section 0.5 ... 0.75 mm
2
(AWG 20 ... 18)
Cable resistance 100 ... 150 at 1 MHz
Capacitance per unit length 40 pF/m (12 pF/ft) at 1 kHz.
For example, the following cable is suitable:
UNITRONIC
®
BUS CAN, 2 x 2 x 0.22 mm
2
by Lappkabel.
Applying the shield Apply the shield at both ends over large area to the electronics shield clamp of the con-
troller and in the housing of the 9-pin Sub-D connector of the operator panel.
Cable length The permitted total cable length is 200 m.
8965662347
n11/ n21*
n12/n22*
X13:
DIØØ
DIØ1
DIØ2
DIØ3
DIØ4
DIØ5
DCOM**
VO24
1
2
3
4
5
6
7
8
9
10
11
MOVIDRIVE
®
RS-485 –
RS-485 +
RS-422 / RS-485
DGND
ST11
ST12
MOVITRAC
®
X45
X46
1
23456HL ^
FSC11B
S1
OFF
ON
7
S2
X44
1
69
5
120 ohms
0.25 W
Enable/rapid stop*
/Controller inhibit
CW/stop*
CCW/stop*
Reference X13:DIØØ...DIØ5
Shield plate or
shield terminal
+24V output
Control unit
DOP11C
Reference potential for binary signals
9-pin D-Sub socket
Jumper between 1 and 6
to activate bus termination
NOTICE
The bus controller may suffer irreparable damage as a result of a short circuit in the
EMC decoupling between the electronics and ground.
Never connect the shield ends to DGND!